{"id":585,"date":"2025-03-24T06:35:21","date_gmt":"2025-03-24T06:35:21","guid":{"rendered":"https:\/\/pineele.com\/?p=585"},"modified":"2025-03-24T06:43:58","modified_gmt":"2025-03-24T06:43:58","slug":"1000-kva-compact-substation-size-dimensions-layout-and-space-requirements","status":"publish","type":"post","link":"https:\/\/pineele.com\/1000-kva-compact-substation-size-dimensions-layout-and-space-requirements","title":{"rendered":"1000 kVA Compact Substation Size: Dimensions, Layout, and Space Requirements"},"content":{"rendered":"\n

\ud83d\udcd8 Introduction to 1000 kVACompact Substation Size\n\n\n\n

A1000 kVA compact substation is a prefabricated, fully integrated solution thatcombines high-voltage switchgear, transformer, and low-voltage switchgear into one enclosure. One of the most critical aspects of planning for such a substation is understanding itsphysical size, footprint, layout, and space requirements.\n\n\n\n

In this guide, we provide a detailed overview of the dimensions of a 1000 kVA compact substation, layout variations, installation clearance standards, and planning considerations. All data is aligned with international best practices and PINEELE’s engineering expertise.\n\n\n\n

\"1000\n\n\n\n
\n\n\n\n

Standard Dimensions of 1000 kVA Compact Substation\n\n\n\n

A typical 1000 kVA compact substation has the following overall dimensions:\n\n\n\n

SectionLength (mm)Width (mm)Height (mm)
HV Compartment1200\u2013160012002200\u20132500
Transformer Comp.2200\u201328001500\u201318002000\u20132300
LV Compartment1200\u201316001200\u201314002000\u20132300
Total Size4500\u201360001800\u201322002200\u20132500\n\n\n\n
\n

Note: Actual sizes vary based on transformer cooling type (oil\/dry), protection devices, access doors, and enclosure design.\n\n\n\n\n


\n\n\n\n

Enclosure Options and Impact on Size\n\n\n\n

The outer enclosure or housing of the compact substation plays a key role in determining the total size:\n\n\n\n

1.Metal Sheet Enclosure (Mild Steel\/GI Painted)\n\n\n\n