\n\n\n\nEnvironmental and Operating Conditions\n\n\n\n
TheZN85-40.5 Vacuum Circuit Breaker is designed to operate reliably in diverse environments:\n\n\n\n\n- Ambient Temperature: -10\u00b0C to +40\u00b0C\n\n\n\n
- Altitude: \u22641500 meters\n\n\n\n
- Relative Humidity: \u226495% (daily), \u226490% (monthly)\n\n\n\n
- Earthquake Resistance: Up to 8 degrees\n\n\n\n
- Free from flammable gases, severe pollution, chemical corrosion, and vibrations\n\n\n\n\n
Applications\n\n\n\n
Thisvacuum circuit breaker is ideal for:\n\n\n\n\n- Power plants and substations\n\n\n\n
- Industrial and mining operations\n\n\n\n
- Medium voltage switchgear (fixed or drawout type)\n\n\n\n
- Systems requiring frequent switching and high short-circuit breaking capacity\n\n\n\n\n
Technical Parameters of ZN85-40.5 Vacuum Circuit Breaker\n\n\n\nElectrical Parameters\n\n\n\nItemUnitValue| Rated Voltage | kV | 40.5 | | Rated Frequency | Hz | 50 | | Rated Current | A | 630, 1250, 1600, 2000, 2500 | | Short-Circuit Breaking Current | kA | 25, 31.5 | | Short-Time Withstand Current (RMS) | kA | 25, 31.5 | | Peak Withstand Current | kA | 63, 80 | | Short-Circuit Closing Current | kA | 63, 80 | | Capacitor Bank Breaking Current (Single\/Back-to-Back) | A | 600 \/ 400 | | Short-Circuit Current Duration | s | 4 | | Short-Circuit Breaking Times | Times | 20 | | Operating Sequence | \u2013 | O-0.3s-CO-180s-CO | | Main Circuit Resistance | \u03bc\u03a9 | \u226465 | | Operating Voltage | V (AC\/DC) | 220 \/ 110 | | Mechanical Life | Times | \u226510,000\n\n\n\n \n\n\n\nMechanical Parameters\n\n\n\nItemUnitValue| Open Contact Gap | mm | 18 \u00b1 1 | | Overtravel | mm | 5 \u00b1 1 | | Contact Bounce Time | ms | \u22643 | | Phase Synchronism | ms | \u22642 | | Average Opening Speed | m\/s | 1.7 \u00b1 0.2 | | Average Closing Speed | m\/s | 0.75 \u00b1 0.2 | | Opening Time | ms | \u226490 | | Closing Time | ms | \u226460 | | Wear Limit (Contact) | mm | 3\n\n\n\n \n\n\n\nMounting & Dimensions (Solid-Seal Type & Insulating Cylinder Type)\n\n\n\nRated Current (A)Breaking Current (kA)Static Contact Size (mm)Plum-Blossom Contact Type| 630 | 20\/25\/31.5 | \u03a635 | CT-30 | | 1250 | 31.5 | \u03a649 | CT-30 | | 1600 | 31.5 | \u03a655 | CT-36 | | 2000 | 31.5 | \u03a679 | CT-48 | | 2500 | 31.5 | \u03a6109 | CT-64\n\n\n\nActuator and Operation Mechanism\n\n\n\n\n- Uses the3AV3 spring operating mechanism known for its maturity and reliability.\n\n\n\n
- Simple design with output curves optimized for the 40.5kV vacuum interrupter\u2019s characteristics.\n\n\n\n
- Mechanism supports both manual and automatic energy storage, enabling local or remote operation.\n\n\n\n\n
TheZN85-40.5 Vacuum Circuit Breaker is a cutting-edge, indoor high-voltage switching device designed for safe and efficient operation in demanding environments. Its compact structure, superior insulation, and mechanical reliability make it an ideal solution for 40.5kV medium voltage systems requiring high short-circuit performance and frequent operation. With a maintenance-free design and strong compliance with international standards, the ZN85-40.5 stands out as a trusted choice in modern power infrastructure.\n","protected":false},"excerpt":{"rendered":"The ZN85-40.5 Indoor Vacuum Circuit Breaker guide is a state-of-the-art medium voltage (MV) power protection device designed for three-phase AC 50Hz, 40.5kV power systems. As a key component in modern substations, power plants, and industrial environments, this vacuum circuit breaker delivers high-performance switching capability for load current, overload current, and fault current scenarios. Its compact […]\n","protected":false},"author":1,"featured_media":1284,"comment_status":"closed","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"footnotes":""},"categories":[36],"tags":[],"class_list":["post-1283","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-vacuum-circuit-breaker"],"acf":[],"yoast_head":"\n | | | | |
|---|
| | | |
|---|
| | | |
|---|